H I Solutions

BACnet Client 7

BACnet (Building Automation and Control Network) is an open communication protocol specifically designed for building automation and control systems

The BACnet Client 7 delivers effective BACnet/IP integration, mapping up to 1,024 points with simple web setup and full unitary controller functionality

The BACnet Client 7 is a straightforward BACnet device that maps unitary controller points to BACnet/IP, allowing monitoring and control of up to 1,024 points from as many as 20 BACnet devices on the unitary LAN. Multiple clients can be added for larger systems, each using a single network address, and point mapping is easily configured through a web interface. It includes full unitary controller functions—such as schedules, trends, globals, and a point database—and is supported by PC Central software, with optional onboard physical I/O for added flexibility.

  • Easy integration of BACnet equipment into the Field
    Commander management system
  • Universal applications configured by software
  • Scheduling by time and day-of-week (plus holidays and
    dates with FC) with onboard clock and calendar
  • Back-up scheduling automatically activated in the event
    of a Unitary LAN failure
  • Alarm reporting with user-defined messages
  • Interactive real-time monitors with multiple actions
  • Optimized start-up and shutdown
  • 25 available general purpose internal event timers
  • Trend and run-time logging
Specifications
Services:

I Am

Who I

Read Property

Write Property

BIBBS Supported:

DS-RP-B-

DS-WS-B –

DS-DDB-B –

(Data Sharing – ReadProperty – B)

(Data Sharing – WriteProperty – B)

(Data Management – Dynamic Device Binding – B)

Object Types:

Device

Analog Input

Analog Output

Analog Value

Binary Input

Binary Output

Binary Value

Multi-state Input

Multi-stat Output

Multi-state Value

Data Link Layer Options:

BACnet IP (Annex J)

Segmentation Capability:

None

Character Sets Supported:

ANSI X3.4

Documentation
Product Brief

PDF: BACnet Client 7 Product Brief

FC-7 Manual

PDF: FC-7 Manual BACnet Integration